UV-IR Flame Detectors

UV-IR Flame Detectors   download


    ELECTRIC SPARK DETECTOR / FIRE CONTROLLER

    UV-IR Flame Detector is a combination of a UV andIR flame detector which utilizes a microprocessor for sophisticated electronic signal analysis. When a UV optical sensor is integrated with an IR sensor, a dual band detector is created that is sensitive to the UV and IR radiation emitted by a flame. The combined UV-IR flame detector offers increased immunity over the UV detector, operates at moderate speeds of response, and is suited for both indoor and outdoor use.

  • Highly Sensitive - detects cigarette lighter flame from 5 meters.
  • Flame detection exceeding 50 meters.
  • Scans an area instead of spot detection.
  • Fast Response Time.
  • Solar and artificial light blindness.
  • Rugged electronic, module.
  • Weather Proof / Explosion proof housing.
  • Design for used in hazarduous /non hazarduous locations.
  • Low power consumption 12/24 VOC or 220 VAC Operation
Technology UV-IR Technology
Response Time < 3 seconds
Cone of vision 120 minimum
Optical Self-Test Automatic continuous optical path
Alarm Reset Automatic or manual when flame is no longer detected
Communication Available with optional MODBUS (RS-485) facility / HART
Operating Temperature 40F to 185F (-40C to 85C)
Dimensions 125 X 125 X 71 mm
Compliance EN 54-10

The above Parameter and Ranges are only indicative. Endee will build up and supply the analyser with Parameters, range and features to any Practical Configuration.

Note : Specifications and Features will vary with application. The above are established and validated during design, but are not to be construed as test criteria for every product. Due to endee's commitment to research, design and product improvement, specifications are subject to change without notice

Approximate Detection Distance for Burning Materials

Cigarette Lighter 1 inch flame from 5mtr
Alcohol 30mtrs(lxlft.Panfire)
Gasoline 50mtrs(lxlft.Panfire)
Jet Fuel 50mtrs(lxlft.Panfire)
Butane 05 mtrs. (lxl inch flame)
Hydrogen Fuel 75 mtrs (6x6 inch Pan fire)
02 Ranges 0-5 Vol% to 0-25 Vol%
Electric Spark 50mtr5.(15VACorDC)

The above Parameter and Ranges are only indicative. Endee will build up and supply the analyser with Parameters, range and features to any Practical Configuration.

Note : Specifications and Features will vary with application. The above are established and validated during design, but are not to be construed as test criteria for every product. Due to endee's commitment to research, design and product improvement, specifications are subject to change without notice